|
Mechanical Systems: |
| |
|
|
-
The facility HVAC system is operated by a
Trane Summit Building Automation System (BAS) that was installed
along with chiller units in 2000. Heat for the building is supplied
by a Con-Edison steam main that enters through a station located in
the building’s sub-basement. The high-pressure steam is utilized to
power the building’s absorption chillers, various-air handling unit
preheat and heating coils, as well as for steam-to-water heat
exchangers that provide heating water to perimeter induction units.
The pressure is lowered by pressure reducing stations at multiple
locations. Condensed steam is returned through a condensate piping
system.
|
-
A chiller plant located in the penthouse
mechanical room provides chilled water for cooling. Cooling is done
by two Trane 380-ton steam powered, lithium bromide, absorption
chiller units that are located at the penthouse level. Heat
rejection for the chillers is by an upper penthouse level Marley
Doubleflow Aqautower cooling tower originally constructed in 1962
and rebuilt in 1999-2000. The chillers have dedicated chilled water
and condenser water horizontal split case Weinman pumps driven by
Baldor 40-HP and 20-HP electric motors. Each chiller has a nominal
rating of 380 tons and uses R-22 as a refrigerant. The chiller
units, associated pumps and other related components were installed
in 2000. The cooling tower components were refurbished in 1999-2000
and have new PVC fill, stainless steel basin and decks, valving,
motors and gear boxes. The building features two roof-level cooling
towers, each with a capacity of 2,500 tons.
|
|
|
-
Air distribution is by two systems,
interior and perimeter, that are divided into low-rise and high-rise
zones. The interior areas are served by air handling units, which
have been converted to a variable air volume (VAV) system. There are
a total of seven air handling units which serve various areas of the
building. The low-rise zone is served by two units, with one
handling the interior areas and the other handling the perimeter
areas. The high-rise zone is served by two more units. The fifth and
sixth handling units serve the concourse, basement and retail units,
as well as the lobby level. A final unit serves the sub-basement
level.
|
-
The perimeter areas are served by a
two-pipe perimeter induction system. There are approximately 40 to
50 perimeter induction units (PIU) per floor at the lower floors and
approximately 30 PIUs per floor on the smaller upper floor areas.
The units are located within cabinets at the floor along the outside
wall. Room air is circulated through grills on the top of the
cabinets. Two supply risers, north and south, supply air to the
induction units. The coils in the induction units are supplied with
heated or chilled water by a secondary water system and each unit
has an individual knob-controlled thermostat.
|
-
Stairwells, bathrooms, and other areas are
ventilated by mechanical exhaust fans. Large capacity ventilation
fans, mounted on the roof, are connected by concealed ducts to each
ventilated space.
|
|
Electrical Systems: |
| |
-
The electrical supply lines run
underground with incoming service from West 40th Street. Electricity
to the building is supplied from underground feeders to the main
switch gear at the meter room located at the sub-basement level. The
main electrical service for the building is provided by a single
central terminal and is 20,000 amperes and 277/480 volt with
three-phase four-wire alternating current. Electrical wiring is
copper installed in metallic conduit.
|
-
Electrical service to each tenant unit
ranges between a minimum of 200 amperes and a maximum of 600 or more
amperes. Commercial units are sub-metered, with circuit breakers
housed in each level’s electrical closet. Circuit breakers
individually supply each unit’s HVAC system, appliances, and
receptacles. Tenant units also include incandescent and fluorescent
light fixtures.
|
|
|
| |
|
|